Single Pulse Generation (Software Start Trigger)
Description
Single pulse generation creates a single pulse after the counter is armed. Depending on the type of counter, it may be possible to specify the delay and pulse width.
Common Applications
8253 counters:
The 8253 counter (used on LabPC, 512, 700, and 1200 series) can generate a pulse with a specifiable delay (in units of source pulses). However, the width of the pulse is one source cycle. Use mode 4.

Mode 4 Timing Diagram
Am9513 based counters:
The Am9513 counters can generate a pulse with the delay and the width user-specifiable. Use CTR Pulse Config.vi or CTR_Pulse.
DAQ_STC based counters:
The DAQ_STC counters can generate a pulse with the delay and the width user-specifiable. See examples that ship with LabVIEW for detailed programming procedure.

Single Pulse Generation
The NI-TIO counters (presently used only on the PCI-6601/6602/6608 boards) can also generate pulses with specifiable delay and width. See examples that ship with LabVIEW for detailed programming procedure
Reader Comments | Submit a comment »
Legal
This tutorial (this "tutorial") was developed by National Instruments ("NI"). Although technical support of this tutorial may be made available by National Instruments, the content in this tutorial may not be completely tested and verified, and NI does not guarantee its quality in any way or that NI will continue to support this content with each new revision of related products and drivers. THIS TUTORIAL IS PROVIDED "AS IS" WITHOUT WARRANTY OF ANY KIND AND SUBJECT TO CERTAIN RESTRICTIONS AS MORE SPECIFICALLY SET FORTH IN NI.COM'S TERMS OF USE (http://ni.com/legal/termsofuse/unitedstates/us/).