Set Timeouts VI

LabVIEW 2017 Real-Time Module Help

Edition Date: March 2017

Part Number: 370622R-01

»View Product Info
Download Help (Windows Only)

Owning Palette: Utilities VIs

Requires: DSC Module or Real-Time Module

Sets both read and write operation timeouts on a Modbus slave.

You can also use the Property Node to set the read operation timeout, write operation timeout, or both timeouts.

Details  

Modbus master in specifies the reference to the Modbus master instance. Use the Create Master Instance VI to create a Modbus master instance.
read operation timeout specifies the read operation timeout in milliseconds. If you specify -1 for read operation timeout, the read operation does not time out until the Modbus slave responds.
write operation timeout specifies the write operation timeout in milliseconds. If you specify -1 for write operation timeout, the write operation does not time out until the Modbus slave responds.
error in describes error conditions that occur before this node runs. This input provides standard error in functionality.
Modbus master out returns a duplicate of Modbus master in.
error out contains error information. This output provides standard error out functionality.

Set Timeouts Details

The Set Timeouts VI enables you to use a single Modbus master instance to perform read or write operations with different timeouts on different Modbus slaves simultaneously, as shown in the following block diagram:

The following list describes important details about the previous diagram:

When the TCP master instance 1 output performs read and write operations on a Modbus slave, the timeouts are both 5,000 ms, which is the default value.
When the TCP master instance 2 output performs read operations on a Modbus slave, the timeout is 4,000 ms. When this output performs write operations, the timeout is 6,000 ms.