Company Events Academic NI Developer Zone Support Solutions Products & Services Contact NI MyNI

Alarming:HiHi:Deadband Property

LabVIEW 8.5 Help
August 2007

NI Part Number:
371361D-01

»View Product Info

Property of Variable.

Gets or sets the HI_HI alarm deadband as a percentage of the full scale range. To use this property, you must install the LabVIEW Datalogging and Supervisory Control Module.

A shared variable does not return to a normal state until it has left the alarm condition set by the value of the Alarming:HiHi:Level property by at least the value of the deadband. If you set the deadband too high, the shared variable value might not clear the alarm.

Note  You can enable alarming only for network-published shared variables.

Remarks

The following table lists the characteristics of this property.

Available in Run-Time Engine and Real-Time Operating SystemNo
PermissionsRead/Write
Settable when the VI is runningYes
Loads the front panel into memoryNo
Need to authenticate before useNo
Loads the block diagram into memoryNo
Remote access disallowedNo
Must wait until user interface is idleNo
Available with control VIsNo
Available with global VIsNo
Available with strict type definitionsNo
Available with polymorphic VIsNo

Resources


 

Your Feedback! poor Poor  |  Excellent excellent   Yes No
 Document Quality? 
 Answered Your Question? 
Add Comments 1 2 3 4 5 submit