Converting NI 9207 Data (FPGA Interface)

NI CompactRIO Device Drivers Help

Edition Date: December 2017

Part Number: 373197L-01

»View Product Info
Download Help (Windows Only)

Set the Calibration Mode to Calibrated in the C Series Module Properties dialog box for the NI 9207 if you want the FPGA I/O Node to return calibrated, fixed-point data from the module. Set the Calibration Mode to Raw if you want the FPGA I/O Node to return calibrated, binary data from the module. If you set the Calibration Mode to Raw, you must convert the binary values to engineering units. You must convert these values in the host VI.

Using an Equation to Convert Binary Current Values to Amperes

You can use the following equation in the host VI to convert binary current values to amperes:

Amps = Binary Value × 0.022 A ÷ 8,388,607

where Binary Value is the value returned by the FPGA I/O Node.

Using an Equation to Convert Binary Voltage Values to Volts

You can use the following equation in the host VI to convert binary voltage values to volts:

Volts = Binary Value × 10.4 V ÷ 8,388,607

where Binary Value is the value returned by the FPGA I/O Node.